IHKA (integrated automatic heating / air conditioning system) RR

The IHKA is used to adapt the climate in the vehicle to the individual needs of the passengers. Information is exchanged between the vehicle components and the IHKA control module via the K-CAN SYSTEM data bus.

Main functions (see corresponding individual function description)

Components

Control module/operating module

The IHKA control module records the signals of the IHKA components and controls/regulates the heating and air conditioning process. The IHKA control module causes the rear-window defroster to be activated and deactivated by the power module.

The control module functions at the same time as operating unit: The temperature selectors for the driver and passenger area as well as the adjusting wheel for the automatic window defrosting/defogging are integrated. The blower adjusters for the driver and passenger area, as well as the block of three switches for recirculated air, rear window heating and air conditioner OFF are directly connected to the front of the control module by plug-in connections.

No distinction is made for left-hand drive and right-hand drive vehicles: The control module/operating module is located on the same vehicle co-ordinates for both vehicles.

Rear compartment control panel

The rear compartment control panel does not have its own processor, only switching elements. It is connected directly to the control module by means of a 12-pin cable.

The temperature selectors for the rear left and right are integrated in the rear compartment control panel.

Heater/air conditioner

The IHKA air conditioner is mounted underneath the instrument cluster on the bulkhead in the middle.

The air conditioner fulfills the following tasks:

The air conditioner is made up of the following components/functional units:

Refrigerant compressor (KMV)

The refrigerant compressor (KMV) compresses the refrigerant gas drawn in by the evaporator and forces it to the condenser. It is always in operation when the vehicle engine is running. Infinitely output regulation is possible on account of its design and activation of a regulating valve with pulse-width-modulated signals by the control electronics. For the purpose of load reduction, only the refrigerating output that is directly needed is generated. The control and switching criteria for this purpose are:

Exchange of information between the IHKA and DME takes place via the body data bus CAN SYSTEM.

NOTE: The compressor must be broken in without fail in the following cases:

Compressor breaking-in:To ensure fault-free compressor lubrication, it is necessary to mix the amount of oil added by the manufacturer uniformly with the liquid refrigerant. For this purpose, the compressor must be operated for a specific period at a speed of between 300 and 1500 rpm.

If the engine idle speed exceeds 1500 rpm, the breaking-in procedure is automatically cut off and a message issued. The breaking-in procedure must then be repeated in its entirety.

Specifications: The air conditioning must be set to OFF when the engine is started. Do not switch on the air conditioning before being prompted.

Carry out the following steps:

Coolant pressure sensor

The pressure sensor in the pressure line between the condenser and the evaporator supplies the control electronics with signals relating to the system pressure.

Condenser with integrated drier

The thermal energy generated by compression of the refrigerant gas in the heat exchanger is dissipated by air cooling to the surroundings at the condenser surface. The refrigerant condenses and turns liquid. In order to prevent corrosion damage, any water present in the refrigerant circuit is bound in the integrated drier. The drier insert can be replaced. It incorporates a filter shield to provided protection against particles.

Auxiliary water pump

An electric auxiliary water pump is installed in order to ensure adequate water flow through the heat exchanger at low engine speeds.

Water valves

The water valves on the left and right serve to regulate the heat exchanger. The water valves are activated with pulse-width-modulated signals. The control module calculates the valve opening times dependent on certain input variables, e.g. engine speed. The valve opening times are 0 ms at max. COLD and 3600 ms at max. WARM.

Microfilter/air intake

A microfilter is located in both of the filter housings for the intake of air. The microfilter is a combination of a particle and activated charcoal filter. The activated charcoal filter holds back disruptive and toxic gases.

Air flap modules

In addition to the step motors fitted in the heating and air conditioning system, 10 other MUX motors (see above) are used. These are connected to the control module across two other motor buses.

The step motors are use to adjust the following ventilation flaps:

Potentiometer air vents

The air volume and distribution can be adapted to the needs of the occupants by manual intervention. To do so, the control module takes account of the potentiometer setting and activates the step motors to bring the ventilation flaps into the corresponding position.

Hall sensors, knee vents

In each case a Hall sensor reports to the control module whether the ventilation flaps at the knee vents are to be opened or closed on the driver's and passenger's side.

AUC sensor

The AUC sensor registers the pollution gas content of the outside air and reports it to the control module as a pulse-width-modulated signal. The evaluation electronics necessary for this sensor is integrated in the sensor. After vehicle start, the sensor always needs a warm-up time of 60 seconds.

Solar sensor

A solar sensor is fitted to the dashboard. It provides two voltage signals that are proportional to the heat generated by solar radiation to which the occupants are subjected at the front left and right.

Auxiliary fan

The auxiliary fan is needed to cool the condenser. The required fan speed depends on the refrigerant pressure and is transferred by the IHKA across the body CAN SYSTEM data bus.

At vehicle speeds > 80 km/h, the auxiliary fan is switched off. At speeds below 70 km/h, the auxiliary fan is switched on again.

CAN messages

The IHKA communicated with various other control modules across the body CAN SYSTEM data bus:

Safety function

Load deactivation

In the case of a ”control system peak reduction priority” signal from the power module, the consumers have their power output reduced or are shut down by the IHKA control system according to priority:

In the case of a ”stationary consumers status” signal - DEACTIVATION by the power module, the stationary consumers are deactivated by the IHKA control system.

The DEFROST function is relevant to safety and always operates at maximum blower output.

Sleep/wait/power down modes

Sleep mode:In order to achieve the required closed circuit current consumption, the control module is intentionally switched via the network management into a state of minimum current consumption (< 100 A). The wait mode must be taken into account here.

Wait mode:The wait mode starts after the following overshoot times have elapsed:

Overshoot time of control module

Terminal 15

Conditions for residual heat

3 minutes

OFF

are not fulfilled

15 minutes

OFF

are fulfilled

Power down mode:With the power down command, the vehicle electrical system is placed for the purpose of rapid closed circuit current measurement in a state that it would normally adopt automatically after the overshoot time has elapsed.

The command is given with the DIS Tester. The overshoot time is thus reduced to max. 5 seconds.