Voltage Supply and Main Relay DDE 4.1
Function
The voltage supply to the DDE control units takes place in the following steps:
- At ignition ON, voltage is applied via terminal 15 to the DDE master control unit
- The DDE master control unit switches both DDE main relays via S_HR
- The DDE main relay 1 switches terminal 30 via U_HR to the DDE master control unit
- The DDE main relay 2 switches terminal 30 via U_HR to the DDE slave control unit
Troubleshooting
The following faults are monitored in the voltage supply system:
- Fault code 2800 (master), 2801 (slave): Voltage supply to DDE control unit exceeded/below specified value
- Fault code 3510 (master), 3511 (slave): DDE main relay switches too early or too late